User's Manual
Table Of Contents
- Table of Contents
- SITRANS LR 460
- Specifications
- Installation
- Wiring
- 4-20 mA Start Up
- Local Operation
- LCD menu structure
- HART Communications
- Remote operation via PROFIBUS PA
- PROFIBUS PA Profile Structure
- Appendix A: Parameter Descriptions
- 1. Identification
- 2. Input
- 3. Output
- 5. Maintenance settings
- 6. Condensed Status Setup
- 6.1. Condensed Status Mode
- 6.1.1. Loss of Echo S0 (Status; Diagnosis)
- 6.1.2. Cable Fault S1 (Status; Diagnosis)
- 6.1.3. No Tech Power S2 (Status; Diagnosis)
- 6.1.4. Device Lifetime Maintenance Required Limit S3 (Status; Diagnosis)
- 6.1.5. Device Lifetime Maintenance Demanded Limit S4 (Status; Diagnosis)
- 6.1.8. Sensor Lifetime Maintenance Demanded Limit S7 (Status; Diagnosis)
- 6.1.9. Device Service Maintenance Required Limit S8 (Status; Diagnosis)
- 6.1.10. Device Service Maintenance Demanded Limit S9 (Status; Diagnosis)
- 6.1.11. LTB Scale S10 (Status; Diagnosis)
- 6.1.12. Internal Temp Sensor S11 (Status; Diagnosis)
- 6.1.13. Internal Temp High S12 (Status; Diagnosis)
- 6.1.16. AIFB2 PV Range S15 (Status; Diagnosis)
- 6.1.19. Calibration Schedule Maintenance Demanded Limit S18 (Status; Diagnosis)
- 6.1.30. Memory EEPROM S29 (Status; Diagnosis)
- 6.1.31. Memory EEPROM Flags S30 (Status; Diagnosis)
- 6.1.32. Memory Flash S31 (Status; Diagnosis)
- 6.1.33. Ident Violation S32 (Status; Diagnosis)
- 6.1.34. Internal Temperature Calibration S33 (Status; Diagnosis)
- 6.1. Condensed Status Mode
- Appendix B: Technical Reference
- Appendix C: Troubleshooting
- Appendix D: Maintenance
- Appendix E: Software Revision History
- Glossary
- Index
Page 59 SITRANS LR 460 – INSTRUCTION MANUAL 7ML19985JM01
mmmmm
Parameters
1.2.4. Master Reset
1.2.5. Reset Fault
Resets the Fault message after an active fault has occurred and been corrected.
This is required only for faults listed as requiring a manual reset in the General
Fault Code list (see page 51).
To reset, key in the value of the fault code in question.
1.2.6. Menu Timer
Determines the length of time (in seconds) the device will stay in PROGRAM mode
without any key presses occurring.
1.2.7. Backlight
Allows you to increase the contrast of the LCD.
1.3. Device
Manufacturer
References a specific manufacturer, usually the name of the company
responsible for the manufacture of this Field Device.
Product designation
Uniquely identifies the Field Device when combined with the Manufacturer
Identification and Device Type. This variable cannot be modified by the Host user.
Device Serial Num
Uniquely identifies the Field Device. This variable cannot be modified by the Host.
Order No.
The order number for this device.
Date of birth
Date of manufacture.
1.3.1. Software Revision
Corresponds to the software or firmware that is embedded in the Field Device.
1.3.2. Loader Revision
Corresponds to the software used to update the Field Device.
Note: Following a Master Reset, complete reprogramming is required.
Values
1
Reset all parameters (except PROFIBUS address) to PROFIBUS PA
profile default values
2506 Warm Start: restart the device (this option is rarely used)
2712 Reset PROFIBUS address to 126
32768 Reset to manufacturer’s default values (factory settings)
Values
0 to 2 Adjusts contrast.