3. Connect the earth conductor of the power supply to the earth terminal on the
metal bracket inside the connection box. Adjust the cable length so that the earth
conductor would be last to disconnect if cable is pulled.
4. Tighten the cable gland and check the strain relief (pull and turn).
5. Screw the cover onto the connection box and hand tighten it. The sealing ring must
be clean and undamaged.
6. Reattach the cover lock on the connection cover.
1.
Install in accordance with
Wiring and Installation
in the HART Application Guide
(order number HCF_LIT-34), available from :
http://www.hartcomm.org/technical/doclist.html
.
2.
Install in accordance with
PROFIBUS PA User and Installation Guidelines
(order
number 2.092), available from www.profibus.com.
1264
5
378
L
1
L
2
N
mA
Rated temperature of
connection cables must
exceed m aximum ambient
temperature by at least 15 K
1264
5
378
L
1
L
2
N
Rated temperature of
connection cables must
exceed maximum ambient
temperature by at least 15 K
PROFI-
BUS PA
HART wiring
1
PROFIBUS wiring
2
earth
terminal
earth
terminal
cable clamp
cable clamp
1264
5
378
mA
19-3 0 V
Rated tempera ture of
connection cables must
exceed maximum ambient
temperature by at least 15 K
12645378
PROFI-
BUS PA
19-30 V
Rated temperature of
connection cables must
exceed m aximum ambient
temperature by at least 15 K
HART wiring
1
PROFIBUS wiring
2
earth
terminal
earth
terminal
cable clamp cable clamp