User's Manual

Table Of Contents
Page 67 SITRANS LR 400 – INSTRUCTION MANUAL 7ML19985FH04
mmmmm
Parameters (Profibus PA)
4.2.3: Sensor param-
eter
4.2.3.1: Sensor damp-
ing
Averaging of measuring
signal
Not displayed if a user
tank is selected in
[4.2.2.1].
1 s numerical value
4.2.3.2: Multiple echo Evaluate multiple echo on on
off
4.2.3.3: Echo motion Evaluate echo motion on on
off
4.2.3.4: Window
tracking
Evaluate moving targets off on
off
4.2.3.5: Tank empty
detect
For qualified personnel only
4.2.3.6: Auto fix dis-
tance
For qualified personnel only
4.2.3.7: Fix Dist List For qualified personnel only
4.2.3.7.1 to 4.2.3.7.9:
Fix Dist List values
For qualified personnel only
4.2.3.8: Auto False
Echo suppression
Learns and records the
current signal up to the
suppression distance set-
ting. These signals are
then ignored during oper-
ation.
use use
record
off
4.2.3.9: Auto False
Echo suppression
distance
Defines the end point of
the Auto False Echo
suppression distance
2/3 tank
height
variable
4.2.3.A Hover level Defines (in %) how high
the TVT curve is placed
above echo profile, rela-
tive to largest echo
40% 0 to 100%
4.2.3.B Window
Trigger
Defines position of win-
dow on leading edge of
selected echo, relative to
amplitude
80% 0 to 100%
4.2.4: Level param.
4.2.4.1: Level URV = [1.5]
Parameters (PROFIBUS PA)
Note: For parameter descriptions, please refer to the associated HART parameters on
pages 30 to 58.
Parameter, menu
identification
Description
Factory
Setting
Setting
Possibilities