User's Manual
Table Of Contents
Page 63 SITRANS LR 400 – INSTRUCTION MANUAL 7ML19985FH04
mmmmm
Parameters (Profibus PA)
Parameters (PROFIBUS PA)
Parameters (PROFIBUS PA)
Note: For parameter descriptions, please refer to the associated HART parameters on
pages 30 to 58.
Parameter, menu
identification
Description
Factory
Setting
Setting
Possibilities
1: Auto-Setup
Language local Language of the local
user interface
English English
Deustch
Length unit m cm
m
mm
ft
in
Nozzle height Height flange to top of
tank
0 m numerical value
Tank height Height tank bottom to top 20 m numerical value
Level URV Full scale of level (see
Functional Dimensions
Diagram on page 33)
20 m numerical value
Level LRV Start of scale of level
(See Functional Dimen-
sions Diagram on
page 33)
0 m numerical value
Level damping Damping of level in s 1 s numerical value
Application type Use of the vessel Liquid (pro-
cess)
Liquid (store)
Liquid (process)
Silo1 (solids)
Silo2 (solids)
User tank1
User tank2
Bus address Current bus address 126 0 to 126
2: Display
2.1: Multi-display Display of two measured
values
Level/Signal-
to-noise ratio
in dB
non-editable
2.2: Level Level of measured
medium
m non-editable
2.3: Volume Volume of measured
medium
m
3
non-editable
2.4: Mass For qualified personnel only