Parameters (HART)
4.2.4.3: Level damping (F = 1 s)
Damping of level in s
Set the damping of the level value in seconds. It acts on the analog output, the limit value
monitor and the local display. For damping of the sensor signal, set Parameter 4.2.3.1.
4.2.4.4: MinLim Level (F = 0 m)
Lower limit value of the level (see Functional Dimensions on page 33)
Set the lower limit value of the level as a height above the LRV.
4.2.4.5: MaxLim Level (F = 20 m)
Upper limit value of the level (see Functional Dimensions on page 33)
Set the upper limit value of the level as a height above the LRV.
4.2.4.6: HYST Level (F = 0.5 m)
Hysteresis of the level limit values
Set the hysteresis of the limit values in the units system selected according to Parameter
4.1.1 (see diagram below).
Limit value alarm
Value numerical value
Note: This parameter is also set using Parameter 1.7 (Level Damping).
Value numerical value
Value numerical value
Value numerical value
measuring variable measuring variable
upper limit
value
hysteresis
lower limit
value
limit value
alarm
hysteresis
limit value
alarm
time
time