7ML19985FH04 SITRANS LR 400 – INSTRUCTION MANUAL Page 32
mmmmm
Operation
Parameters (HART)
The parameter groups are followed by the parameters within each group. The parameter
tables show the values you need to enter and are followed by additional information
when necessary. Factory settings are displayed after the parameter name, where
applicable.
Note: Parameter menus are dependent on selections made by the user.
In some cases, parameter menus are renumbered according to the
selection made at the previous menu level. See table below for an
example.
When User chooses Parameter 4.2.2.1:
Application Type = Liquids (Process)
When User chooses Parameter 4.2.2.1:
Application Type = User tank1
4.2.2.
2: Surface
(not available when 4.2.2.1 = User tank1)
4.2.2.3: Deadband 4.2.2.2: Deadband
4.2.2.
4: Correction Factor 4.2.2.3: Correction Factor
4.2.2.5: Filling Speed
(not available when 4.2.2.1 = User tank1)
4.2.2.
6: Reflectivity
(not available when 4.2.2.1 = User tank1)
4.2.2.7: Failsafe Level 4.2.2.4: Failsafe Level
4.2.2.8: Failsafe Timer 4.2.2.5: Failsafe Timer
4.2.2.
9: Range Extension 4.2.2.6: Range Extension