A5E32337683 SITRANS LR260 (HART) – OPERATING INSTRUCTIONS Page 91
mmmmm
B: Troubleshooting
S: 17 Calibration interval as defined in
Maintenance Required Limit has
expired.
Perform calibration.
S: 18 Calibration interval as defined in
Maintenance Demanded Limit has
expired.
Perform calibration.
S: 28 * Internal device failure caused by a
RAM memory error.
Repair required: contact your local
Siemens representative.
S: 29 * EEPROM damaged. Repair required: contact your local
Siemens representative.
S: 31 * Flash error. Repair required: contact your local
Siemens representative.
S: 33 * Factory calibration for the internal
temperature sensor has been lost.
Repair required: contact your local
Siemens representative.
S: 34 * Factory calibration for the device
has been lost.
Repair required: contact your local
Siemens representative.
S: 35 * Factory calibration for the device
has been lost.
Repair required: contact your local
Siemens representative.
General Fault Codes (Continued)
Code /
Icon
Meaning Corrective Action