Page 90 SITRANS LR260 (HART) – OPERATING INSTRUCTIONS A5E32337683
mmmmm
B: Troubleshooting
S: 3 Device is nearing its lifetime limit
according to the value set in Mainte-
nance Required Limit.
Replacement is recommended.
S: 4 Device is nearing its lifetime limit
according to the value set in Mainte-
nance Demanded Limit.
Replacement is recommended.
S: 6 Sensor is nearing its lifetime limit
according to the value set in Mainte-
nance Required Limit.
Replacement is recommended.
S: 7 Sensor is nearing its lifetime limit
according to the value set in Mainte-
nance Demanded Limit.
Replacement is recommended.
S: 8 Service interval as defined in Main-
tenance Required Limit has expired.
Perform service.
S: 9 Service interval as defined in Main-
tenance Demanded Limit has
expired.
Perform service.
S: 11 Internal temperature sensor failure. Repair required: contact your local
Siemens representative.
S: 12 Internal temperature of device has
exceeded specifications: it is operat-
ing outside its temperature range.
Relocate device and/or lower pro-
cess temperature enough to cool
device. Inspect for heat-related
damage and contact your local Sie-
mens representative if repair is
required.
Fault code will persist until a manual
reset is performed using PDM or the
LCD interface.
General Fault Codes (Continued)
Code /
Icon
Meaning Corrective Action