Page 80 SITRANS LR260 (HART) – OPERATING INSTRUCTIONS A5E32337683
mmmmm
Parameters
5. Communication
5.1. Device Address
Sets the device address or poll ID on a HART network. Any address other than 0 will
cause the output current to be a fixed value, and the current will not indicate the
reading.
To set the address via the handheld programmer:
Press RIGHT arrow to activate PROGRAM mode and open menu level 1.
Press DOWN arrow repeatedly to navigate to COMMUNICATION (menu
item 5).
Press RIGHT arrow to display the parameter list.
Scroll to DEVICE ADDRESS and press RIGHT arrow to open parameter view.
Press RIGHT arrow to open Edit mode. Key in a new value and press RIGHT
arrow to accept it.
5.2. Communication Control
Enables /disables the read/write access to parameters via remote communications.
Values
Range: 0 to 15
Default: 0
Note: SITRANS LR260 can only reset this parameter via the handheld
programmer.
Options
Read Only
No changes are permitted via remote
communications.
* Read Write Changes are permitted.
Restricted
Sets the status to Read Only, with the potential
for another HART device to change this via
remote communications.