A5E32337683 SITRANS LR260 (HART) – OPERATING INSTRUCTIONS Page 63
mmmmm
Parameters
Enter a value slightly greater than the vessel’s maximum emptying rate, in
Sensor Units per minute.
2.2.8. Transducer Block (TB) Values
For diagnostic purposes
2.2.8.2. Level Measurement (LEVEL MEAS.)
The value for level. Read Only.
In SIMATIC PDM, open the menu View – Display, and select the tab
Display.
2.2.8.3. Space Measurement (SPACE MEAS.)
The value for space. Read Only.
In SIMATIC PDM, open the menu View – Display, and select the tab
Display.
2.2.8.4. Distance Measurement (DISTANCE MEAS.)
The value for distance. Read Only.
In SIMATIC PDM, open the menu View – Display, and select the tab
Display.
2.3. Output
2.3.1. mA Output
2.3.1.1. mA Output Value
The loop current value in mA. Read Only except if the Manual option is
chosen in mA Output function below (2.3.1.2).
2.3.1.2. mA Output Function (mA OUTPUT FUNC.)
Alters the mA output/measurement function and allows the output to be set
independently.
Options Meters/Minute
Slow 0.1
Medium 1
Fast 10
Values
User Entry only if Manual option is chosen in
2.3.1.2.
Range: 3.6 mA to 22.6 mA
Options
Manual
Level
Space
*Distance