2.2.7. Rate
2.2.7.1. Response Rate
Sets the reaction speed of the device to measurement changes.
Use a setting just faster than the maximum filling or emptying rate
(whichever is faster).
2.2.7.2. Fill Rate (FILL RATE/MIN)
Defines the maximum rate at which the reported sensor value is allowed to
increase. Allows you to adjust the SITRANS LR260 response to increases
in the actual material level. Fill Rate is automatically updated whenever
Response Rate is altered.
Enter a value slightly greater than the maximum vessel-filling rate, in
Sensor Units per minute.
2.2.7.3. Empty rate (EMPTY RATE/MIN)
Defines the maximum rate at which the reported sensor value is allowed to
decrease. Adjusts the SITRANS LR260 response to decreases in the actual
material level. Empty Rate is automatically updated whenever Response
Rate is altered.
Note: Changing Response Rate resets Fill Rate, Empty Rate, Damping
Filter and Echo Lock.
Related
parame-
ters
Response
Rate
Fill Rate
Empty
Rate
Damping
Filter
Echo Lock
Options
slow 0.1 m/min. 0.1 m/min. 10 s
max.
verifications
medium 1 m/min. 1 m/min. 10 s
max.
verifications
* fast 10 m/min. 10 m/min. 0 s
max.
verifications
Values
Range: 0 to 30 m / min.
Default: 10 m/min.
Altered by Response Rate
Related parameters Sensor Units
Options Meters/Minute
Slow 0.1
Medium 1
Fast 10
Values
Range: 0 to 30 m / min.
Default: 10 m / min.
Altered by
Response Rate