User's Manual

Table Of Contents
Page 60 SITRANS LR260 (HART) – OPERATING INSTRUCTIONS A5E32337683
mmmmm
Parameters
2.2.5.3. Auto Suppression Range
Defines the endpoint of the Learned TVT distance. Units are defined in
sensor units.
a. Press RIGHT ARROW to open Edit mode.
b. Enter the new value and press RIGHT ARROW to accept it.
c. Set
2.2.5.2. Auto False Echo Suppression
.
2.2.5.4. Shaper Mode
Adjusts the TVT curve at a specified range.
Values
Range: 0.00 to 30.00 m
Default: 1.00 m
Options
ON
*
OFF
Before Auto False Echo Suppression
default
TVT
Level (db)
echo
marker
After Auto False Echo Suppression
learned
TVT curve
level
Level (db)
false echo
echo
marker