A5E32337683 SITRANS LR260 (HART) – OPERATING INSTRUCTIONS Page 53
mmmmm
Parameters
Operation types
2.2.1.6. Low Calibration Pt. (LOW CALIB. PT.)
Distance from Sensor Reference to Low Calibration Point (corresponding to
Low Level Point). Units are defined in Sensor Units.
1)
2)
2.2.1.7. High Calibration Pt. (HIGH CALIB. PT.)
Distance from Sensor Reference to High Calibration Point (corresponding
to High Level Point). Units are defined in Sensor Units. (See Operation
types for an illustration.)
When setting the High Calibration Point value, note that echoes are ignored
within Near Range (2.2.1.11).
Values
Range: 0 to 30 m.
Default dependent on horn type
1)
The point from which level measurement is referenced. See
Dimensions:
on page 10.
2)
The distance from sensor reference point to the target.
Values
Range: 0 to 30 m.
Default 0 m
Related parameters
2.2.1.12. Near Range
high
calibration
point
low calibration point
level
space
distance
2
sensor reference point
(flange face)
sensor reference point
(flange face)
low calibration point
high calibration point
SITRANS LR260 with Easy Aimer
Level
1