Page 48 SITRANS LR260 (HART) – OPERATING INSTRUCTIONS A5E32337683
mmmmm
SIMATIC PDM
Simulate AO (Analog Output)
Allows you to input a simulated value in order to test the functioning of the mA
connections during commissioning or maintenance of the device.
To simulate a user-defined mA value:
1. Open the menu Device – Simulate AO.
2. Select Other, enter the simulated value, and click on OK. The message ’Field
Device fixed at new value’ appears. Click on OK.
3. When you are ready to end simulation, select End and click on OK to return the
device to the original output level.
HART Communication
Set the number of request/response preambles (minimum 5).
Open the menu Device – HART Communication.
How to Set Device Address
The default address for the device is 0. To reset the address via the handheld programmer see
5.1.Device Address
on page 80.