A5E32337683 SITRANS LR260 (HART) – OPERATING INSTRUCTIONS Page 29
mmmmm
Quick Start: local
Programming SITRANS LR260
Change parameter settings and set operating conditions to suit your specific application.
•See
Operating via SIMATIC PDM
on page 36 for remote operation.
Programming via the handheld programmer
Parameter menus
Parameters are identified by name and organized into function groups, then arranged in a
5-level menu structure (see
LCD menu structure
on page 121).
For the complete list of parameters with instructions, see
Parameter Reference
on page
49.
1. Enter PROGRAM mode
Point the programmer at the display (from a
maximum distance of 500 mm [1.6 ft.]).
RIGHT arrow activates PROGRAM
mode and opens menu level 1.
Mode opens the menu level last
displayed in PROGRAM mode within the last
30 minutes, or menu level 1 if power has
been cycled since then.
Notes:
While the device is in PROGRAM mode, the output remains fixed and does not
respond to changes in the device.
Do not use the handheld programmer at the same time as SIMATIC PDM or erratic
operation may result.
SITRANS LR260 automatically returns to Measurement mode after a period of
inactivity in PROGRAM mode (between 15 seconds and 10 minutes, depending on
the menu level).
Note: For the complete list of parameters with instructions, see
Parameter Reference
on page 49.
1. QUICK START
2. SETUP
2.1. DEVICE
2.2. INPUT
2.2.1. SENSOR CALIB.
2.2.4. ECHO PROC.
Note:
In Navigation mode
ARROW keys move to the
next menu item in the
direction of the arrow.
display
handheld programmer
(ordered separately)
max. 500 mm
(1.6 ft)