Page 108 SITRANS LR260 (HART) – OPERATING INSTRUCTIONS A5E32337683
mmmmm
E: Application Examples
Return to Measurement: press Mode to start normal operation.
Parameter
type
Parameter No. and
Name
Options/
Values
Function
Quick Start
Wizard
parameters
1.1. Application Type
STEEL
1.2. Response Rate
SLOW Slow =0.1 m/minute
1.3. Units
M meters
1.4. Operation
LEVEL Level
1.5. Low Calibration Point
(LOW CALIB. PT.)
16 16 m
1.6. High Calibration Point
(HIGH CALIB. PT.)
0.5 0.5 m
1.7. Apply? (Apply changes)
YES Transfers Quick Start
settings to device.
Independent
parameters
2.4.1. Fail-safe Timer
2 2 minutes
2.4.2. Fail-safe Material
Level (FAILSAFE MAT. LE)
HI Failsafe level set to
High