User's Manual

Table Of Contents
Page 104 SITRANS LR260 (HART) – OPERATING INSTRUCTIONS A5E32337683
mmmmm
D: Technical Reference
Loop power
Typical Connection Drawing
Allowable operating area of SITRANS LR260
Loop Voltage versus Loop Resistance
Note: Loop voltage is the voltage at the terminals of the power supply (not the
voltage at the terminals of the device).
+
-
LR260
loop resistance
RL
loop current IL
loop voltage
power
supply
0
100
200
300
400
500
600
700
800
900
1000
10.00 15.00 20.00 25.00 30.00
RL=44.6*VL - 493.4
RL=272.7*VL - 4554.1
(16.7v, 0 ohms)
(17.8v, 300 ohms)
(30.0v,845 ohms)
ALLOWABLE
OPERATING AREA
Power Supply Requirements
Loop Resistance - RL
Loop Voltage -VL