A5E32337685 SITRANS LR260 (PROFIBUS PA) – OPERATING INSTRUCTIONS Page 77
mmmmm
Parameters
3.4.8. Acknowledge Status (ACK STATUS)
Displays the status of the Maintenance Alerts that have been acknowledged.
3.4.9. Acknowledge (ACK)
Allows you to acknowledge either a Maintenance Required or a Maintenance
Demanded alert.
To acknowledge an alert via SIMATIC PDM:
a) Open the menu View – Device Status and click on the Maintenance tab.
b) In the Device Lifetime section, click on Acknowledge Warnings.
3.5. Remaining Sensor Lifetime (REMAIN SENS. LIFE)
1)
The device monitors the predicted lifetime of the sensor (the components exposed to
the vessel environment).
To access these parameters via SIMATIC PDM, open the menu Device –
Maintenance and select the Remaining Sensor Lifetime tab.
3.5.1. Total Sensor Operating Time (SENS OP. TIME)
Read only. Displays the amount of time the sensor has been operating.
Can be reset to zero via the handheld programmer (after performing a service).
Options (view only)
Maintenance Required Alert acknowledged.
Maintenance Demanded Alert acknowledged.
1)
In device, Maintenance parameters are displayed in years. In SIMATIC PDM, mainte-
nance parameter units are user selectable.