A5E32337685 SITRANS LR260 (PROFIBUS PA) – OPERATING INSTRUCTIONS Page 71
mmmmm
Parameters
2.4.2. Fail-safe Mode FB1 (FS MODE FB1)
Fail-safe Mode occurs if the status of the input value is bad, or if the device has
been put into Fail-safe mode using Simulation. One of three options can be
selected for the material level to be reported when the LOE timer expires.
2.4.3. Fail-safe Value FB1 (FS VALUE FB1)
Accessible in SIMATIC PDM only after Substitute value is selected in Fail-safe
Mode FB1 (FS MODE FB1)(2.4.2.).
User-defined default for the Output Value, if sensor or sensor electronic fault is
detected. Units are the same as the AIFB1 units.
2.4.4. Fail-safe Mode FB2 (FS MODE FB2)
Fail-safe Mode occurs if the status of the input value is bad, or if the device has
been put into Fail-safe mode using Simulation. One of three options can be
selected for the material level to be reported when the LOE timer expires.
2.4.5. Fail-safe Value FB2 (FS VALUE FB2)
Accessible in SIMATIC PDM only after Substitute value is selected in Fail-safe
Mode FB2 (FS MODE FB2)(2.4.4.).
User-defined default for the Output Value, if sensor or sensor electronic fault is
detected. Units are the same as the AIFB2 units.
Material level to be reported
Options
Substitute value (Default value used as output value).
* Last value (Store last valid output value).
Use bad value (Calculated output value is incorrect).
Values
Range: -999.99 to 999.99 m
Default: 0 m
Material level to be reported
Options
Substitute value (Default value used as output value).
* Last value (Store last valid output value).
Use bad value (Calculated output value is incorrect).
Values
Range: -999.99 to 999.99 m
Default: 0 m