Page 70 SITRANS LR260 (PROFIBUS PA) – OPERATING INSTRUCTIONS A5E32337685
mmmmm
Parameters
2.3.1.9.5. Limit Hysteresis
Hysteresis is used to adjust the sensitivity of the trigger for alarm
messages. It is used to compensate when a process variable
fluctuates around the same value as a limit. A high level alarm occurs
when a value exceeds an upper limit. The alarm’s status remains
true until the value drops below the limit minus the alarm hysteresis.
The directions are reversed for low limit detection.
Enter a value for the hysteresis here, to be used for all warnings and
alarms. The units are the same as the Output scale, i.e. AIFB1 units.
2.3.1.10. Human Interface
2.3.1.10.1. Decimal Point
The number of digits to display after the decimal point. (The LCD is
limited to displaying two decimal places in Measurement mode. In
SIMATIC PDM up to seven decimal places may be used to display
measured values.)
2.3.2. AIFB2
(See AIFB1: the parameters for AIFB2 are identical.)
2.4. Fail-safe
2.4.1. LOE Timer
Sets the time to elapse in minutes since the last valid reading, before Fail-safe
State activates
Values
Range: -999.99 to 999.99 m
Default: 0.5% of output scale range
Options
Range: 0, 1, 2, 3, 4, 5, 6, 7
Default: 2
Note: The last valid reading is maintained until the LOE timer expires. After
the timer expires, the reading is set based on Fail-safe Value (see below).
Values
Range: 0 to 720 min.
Default: 10.0 min