Page 66 SITRANS LR260 (PROFIBUS PA) – OPERATING INSTRUCTIONS A5E32337685
mmmmm
Parameters
2.2.6.3. Empty rate (EMPTY RATE/MIN)
Defines the maximum rate at which the reported sensor value is allowed to
decrease. Adjusts the SITRANS LR260 response to decreases in the rate at
which the vessel empties.
Enter a value slightly greater than the vessel’s maximum emptying rate, in
Sensor Units per minute.
2.2.7. Transducer Block Values (for diagnostic purposes)
2.2.7.1. Main Output (PV– Primary Value)
The value for level/volume. Read Only.
In SIMATIC PDM, open the menu View – Display, and select the tab
Measured Value (Secondary Values). Refer to Level/Volume field.
2.2.7.2. Output, no linearization (SV1 – Secondary Value 1)
The value for level. Read Only.
In SIMATIC PDM, open the menu View – Display, and select the tab
Measured Value (Secondary Values). Refer to Level/Volume field.
2.2.7.3. Output, no level offset (SV2 – Secondary Value 2)
The value for distance. Read Only.
In SIMATIC PDM, open the menu View – Display, and select the tab
Measured Value (Secondary Values). Refer to Distance field.
2.3. Output
2.3.1. AIFB1
Static Revision No.
The revision level of the static data associated with Analog Input Function
Block 1. The Static Revision No. is updated whenever a configuration
parameter is changed.
Note: Empty Rate is automatically updated whenever Response
Rate(2.2.6.1.) is altered
Options
Range: 0 to 999.99 m/min.
Slow
0.1 m/min.
Medium
1
m/min.
*
Fast
10
m/min.
Altered by: Response Rate (2.2.6.1.)
Related parameters Unit (Level) (2.2.1.6.)