A5E32337685 SITRANS LR260 (PROFIBUS PA) – OPERATING INSTRUCTIONS Page 55
mmmmm
Parameters
2.2.1.3. Low Calibration Pt. (LOW CALIB. PT.)
Distance from Sensor Reference to Low Calibration Point (corresponding to
Low Level Point). Unit is defined in Sensor units.
1)
2.2.1.4. High Calibration Pt. (HIGH CALIB. PT.)
Distance from Sensor Reference to High Calibration Point (corresponding
to High Level Point). Unit is defined in Sensor units.
2.2.1.5. Limit Sensor Value
When ON, limits sensor value to the range between Low Calibration Point
and High Calibration Point.
2.2.1.6. Unit (Level)
Select engineering units for Level.
2.2.1.7. Low Level Point
The level when the material is at Low Calibration Point. The unit is defined
in Level units.
2.2.1.8. High Level Point
The level when the material is at High Calibration Point. The unit is defined
in Level units.
2.2.1.9. Level Offset
A constant offset that can be added to Level. The unit is defined in Level
units.
Values
Range: 0 to 30 m. Default: 30.000 m (dependent on horn type)
1)
The point from which level measurement is referenced (see
Dimensions
on page 9).
Values
Range: 0 to 30 m. Default: 0.000 m
Options
ON, OFF
Default: ON
Options
M, CM, MM, FT, IN, Percent
Default: Percent
Values
Default: 0%
Values
Default: 100%
Values
Default: 0%