A5E32337685 SITRANS LR260 (PROFIBUS PA) – OPERATING INSTRUCTIONS Page 53
mmmmm
Parameters
Operation types
1.5. Low Calibration Point (LOW CALIB. PT.)
Distance from Sensor Reference to Low Calibration Point: usually process empty
level.
1.6. High Calibration Point (HIGH CALIB. PT.)
Distance from Sensor Reference to High Calibration Point: usually process full level.
1.7. Apply? (Apply changes)
In order to save the Quick Start settings it is necessary to select Yes and apply
changes.
Display shows DONE when Quick Start is successfully completed.
Press Mode to return to Measurement mode.
Values
Range: 0.000 to 30.000 m
Default: horn type dependent
Values
Range: 0.000 to 30.000 m
Default: 0.0 m
Options
NO, YES, DONE
high
calibration
point
low calibration point
level
space
distance
sensor reference point
(flange face)