User's Manual

Table Of Contents
Page 52 SITRANS LR260 (PROFIBUS PA) – OPERATING INSTRUCTIONS A5E32337685
mmmmm
Parameters
Quick Start Wizard
The Quick Start wizard groups together all the settings you need to configure for a simple
application. You can access it either via SIMATIC PDM, or via the handheld programmer.
The Quick Start wizard is a complete package and settings are inter-related.
Do not use the Quick Start wizard to modify individual parameters.
Perform customization of the device only after the Quick Start is completed.
1. Quick Start
1.1. Application Type
1.2. Response Rate
Sets the reaction speed of the device to measurement changes in the target range.
Use a setting just faster than the maximum filling or emptying rate (whichever is
greater). Slower settings provide higher accuracy, faster settings allow for more level
fluctuation.
1.3. Units
Select the units for the Quick Start variables (high and low calibration point, and level,
distance, or space).
1.4. Operation
Options
STEEL
Silo construction
CONCRETE
Default: STEEL
Options
SLOW
0.1 m/minute
MED
1.0 m/minute
FAST
10.0m/minute
Default: FAST
Options
M, CM, MM, FT, IN
Default: M
Options
NO
SERVICE
SITRANS LR260 stops updating measurements. Last valid
measurement value is displayed.
LEVEL
Distance to material surface referenced from Low Calibration
Point (process empty level).
SPACE
Distance to material surface referenced from High Calibration
Point (process full level).
DISTANCE
Distance to material surface referenced from Sensor Reference
Point.
Default: DISTANCE