Page 46 SITRANS LR260 (PROFIBUS PA) – OPERATING INSTRUCTIONS A5E32337685
mmmmm
SIMATIC PDM
Trend
Open the menu View – Trend
Simulation
Simulate Analog Input to AIFB1 or AIFB2
Allows you to input a simulated value in order to test the functioning of the Analog Input
Function Blocks.
1. Open the menu Device – Simulation, and
select the desired function block.
2. Enable simulation.Click on Transfer.
3. Enter a value, quality, status, and click on
Transfer. The LCD displays the substitute
value.
4. After simulation is complete, disable
simulation.
Note: Record the default X-Scale (horizontal axis) and Data Scale (vertical axis) values
so that you can restore the default view by resetting to these values.
Note: The Simulation parameter influences output to the control system.
PERCENT
[]
AIFB 1
21.40 °C
SUBSTITUTE VAL.
40.61