Page 44 SITRANS LR260 (PROFIBUS PA) – OPERATING INSTRUCTIONS A5E32337685
mmmmm
SIMATIC PDM
Auto False Echo Suppression
SITRANS LR260 first learns the echo profile. Then the learned profile, or part of it, is used to
screen out false echoes. (See
Auto False Echo Suppression
on page 105 for a more detailed
explanation.)
1. Determine Auto Suppression Range (the distance within which the learned TVT will
replace the default TVT). Measure the actual distance from the antenna reference
point to the material surface using a rope or tape measure, and make allowances
for the actual location of the LR260. Subtract 2 m (6.56 ft) from this distance, and use
the resulting value.
2. Open the menu Device – Auto False Echo Suppression.
3. Enter the value for Auto Suppression Range and click on Set Range.
4. Click on Learn. While the new curve is being learned, all buttons are inaccessible.
Unless calculation is instantaneous, buttons will disappear until it is complete.
5. When the buttons are visible, click on Close. Auto TVT is now on, and the learned
TVT curve will be used.
6. To turn Auto False Echo Suppression off or on, re-open menu Device – Auto False
Echo Suppression and click on Off or On.
Notes:
If possible, adjust Auto False Echo Suppression parameters with an empty or almost
empty vessel. There should be a minimum distance of 2 meters from the radar
instrument to the material.
Set Auto False Echo Suppression and Auto Suppression Range during installation, if
possible.
Before adjusting these parameters, rotate the instrument for best signal (minimum
false-echo amplitude).