Page 34 SITRANS LR260 (PROFIBUS PA) – OPERATING INSTRUCTIONS A5E32337685
mmmmm
Quick Start: local
1.4. Operation
1)
1.5. Low Calibration Point
Distance from Sensor Reference to Low Calibration Point: usually process empty
level. (See 1.4. Operation for an illustration.)
1.6. High Calibration Point
Distance from Sensor Reference to High Calibration Point: usually process full level.
(See 1.4. Operation for an illustration.)
1.7. Apply? (Apply changes)
In order to save the Quick Start settings it is necessary to select Yes to apply
changes.
Press Mode to return to Measurement mode. SITRANS LR260 is now ready to operate.
Operation
types
NO
SERVICE
SITRANS LR260 stops updating measurements. Last valid
measurement is displayed.
LEVEL
Distance to material surface referenced from Low Calibration
Point (process empty level).
SPACE
Distance to material surface referenced from High Calibration
Point (process full level).
DISTANCE
Distance to material surface referenced from Sensor Refer-
ence Point.
Default: DISTANCE
1)
The point from which High and Low Calibration points are referenced: see
Dimensions
on page 9.
Values
Range: 0.0000 to 30.000 m
Default: horn type dependent
Values
Range: 0.0000 to 30.000 m
Default: 0.0 m
Options
YES, NO, DONE
(Display shows DONE when Quick Start is successfully completed)
high
calibration
point
low calibration point
level
space
distance
sensor reference point
(flange face)