User's Manual

Table Of Contents
Page 30 SITRANS LR260 (PROFIBUS PA) – OPERATING INSTRUCTIONS A5E32337685
mmmmm
Quick Start: local
Programming SITRANS LR260
Change parameter settings and set operating conditions to suit your specific application.
•See
Operating via SIMATIC PDM
on page 37 for remote operation.
Programming via the handheld programmer
Parameter menus
Parameters are identified by name and organized into function groups, then arranged in a
5-level menu structure (see
LCD menu structure
on page 141).
For the complete list of parameters with instructions, see
Parameter Reference
on page 51.
1. Enter PROGRAM mode
Point the programmer at the display (from a
maximum distance of 500 mm [1.64 ft]).
RIGHT arrow activates PROGRAM
mode and opens menu level 1.
Mode opens the menu level last
displayed in PROGRAM mode within the last
30 minutes, or menu level 1 if power has been
cycled since then.
Note: While the device is in PROGRAM mode the output remains active and continues
to respond to changes in the device.
Notes:
The Quick Start wizard settings are inter-related and changes apply only after you
click on Apply at the end of the Quick Start steps.
Do not use the Quick Start wizard to modify individual parameter: see
instead
Parameter Reference
on page 51.
SITRANS LR260 automatically returns to Measurement mode after a period of
inactivity in PROGRAM mode (between 15 seconds and 10 minutes, depending on
the menu level).
display
handheld programmer
Max. 500 mm
(1.64 ft)