Page 128 SITRANS LR260 (PROFIBUS PA) – OPERATING INSTRUCTIONS A5E32337685
mmmmm
G: Communications PA
Acyclic Extended Diagnostics /General Fault Codes
LCD
display
Meaning Corrective Action Byte Bit
S:0
The device was unable to get a
measurement within the LOE
Fail-safe Timer period. Possible
causes: faulty installation,
material buildup, foaming/other
adverse process conditions,
invalid calibration range.
Ensure installation details are
correct. Ensure no material
buildup. Clean if necessary.
Adjust process conditions to
minimize foam or other adverse
conditions. Correct range
calibration. If fault persists,
contact your local Siemens
representative.
0
0
S:2
Unable to collect profile
because of a low power
condition that is outside of the
operating range of the device.
Repair required. Contact your
local Siemens representative.
2
S:3
Device is nearing its lifetime
limit according to the value set
in Maintenance Required Limit.
Replacement is recommended.
3
S:4
Device is nearing its lifetime
limit according to the value set
in Maintenance Demanded
Limit.
Replacement is recommended.
4
S:6
Sensor is nearing its lifetime
limit according to the value set
in Maintenance Required Limit.
Replacement is recommended.
6
S:7
Sensor is nearing its lifetime
limit according to the value set
in Maintenance Demanded
Limit.
Replacement is recommended.
7
S:8
Service interval as defined in
Maintenance Required Limit
has expired.
Perform service.
1
0
S:9
Service interval as defined in
Maintenance Demanded Limit
has expired.
Perform service.
1
S:10
Input parameters High
Calibration Point and Low
Calibration Point are the same.
Check calibration settings of
device. Ensure settings for High
Calibration Point and Low
Calibration Point are different.
2