User's Manual

Table Of Contents
Page 124 SITRANS LR260 (PROFIBUS PA) – OPERATING INSTRUCTIONS A5E32337685
mmmmm
G: Communications PA
Status Byte
When Condensed Status is disabled, Status Byte will be returned, and the following
codes will be used.
Condensed Status
Hex
value
Status BAD Description
0x00 BAD – non specific
Proxy determines that a device does not
communicate.
0x23
BAD – passivated (diagnostics
alerts disabled)
Configured failsafe value is used,
accompanied by this status.
0x24
...0x27
BAD – maintenance alarm, more
diagnosis available
No measurement available because of a
failure.
0x2B
BAD – process related, no mainte-
nance
No measurement available because of
invalid process conditions.
0x3C
...0x3F
BAD – function check / local over-
ride, value not usable
Occurs during cleaning or calibration
process.
Status Codes for Good Quality
Values in hex notation Description
0x80 Data is GOOD.
0x84...0x87
A parameter in the function block has been changed: status active
for 20 s
0x89 Active low warning.
0x8A Active high warning.
0x8D Active low alarm.
0x8E Active high alarm.
Status Codes for Uncertain Quality
Values in hex notation Description
0x4B Value is a substituted value (normally used in Failsafe).
0x4C...0x4F Initial value.
0x44...0x47 Last usable value.