A5E32337685 SITRANS LR260 (PROFIBUS PA) – OPERATING INSTRUCTIONS Page 95
mmmmm
B: Troubleshooting
General Fault Codes
Data exchanged
No data exchange
Write access enabled
Write access disabled
Notes:
If more than one fault is present, the device status indicator and text for each fault
alternate at 2 second intervals.
Some faults cause the device to go to Fail-safe mode (Fault 52). These are indicated with
an asterisk (*).
General Fault Codes
Code /
Icon
Meaning Corrective Action
S: 0 * The device was unable to get a mea-
surement within the Fail-safe LOE
Timer period. Possible causes: faulty
installation, antenna material
buildup, foaming/other adverse pro-
cess conditions, invalid calibration
range.
Ensure installation details are cor-
rect. Ensure no antenna material
buildup. Clean if necessary. Adjust
process conditions to minimize foam
or other adverse conditions. Correct
range calibration. If fault persists,
contact your local Siemens repre-
sentative.
S: 2 * Unable to collect profile because of
a power condition that is outside of
the operating range of the device.
Repair required: contact your local
Siemens representative.
S: 3 Device is nearing its lifetime limit
according to the value set in Mainte-
nance Required Limit.
Replacement is recommended.
S: 4 Device is nearing its lifetime limit
according to the value set in Mainte-
nance Demanded Limit.
Replacement is recommended.
Icon
Priority
Level
Meaning (cont’d)