User's Manual
Table Of Contents
- Table of Contents
- SITRANS LR250 Overview
- Specifications
- Installation
- Wiring
- Operating via the handheld programmer
- Operating via SIMATIC PDM
- Functions in SIMATIC PDM
- Quick Start Wizard via SIMATIC PDM
- Changing parameter settings using SIMATIC PDM
- Parameters accessed via pull-down menus
- Operating via AMS Device Manager
- Functions in AMS Device Manager
- Features of AMS Device Manager
- Device Description (DD)
- Configuring a new device
- Startup
- Pull-down menu access
- Device configuration
- Quick Start Wizard via AMS Device Manager
- Maintenance and Diagnostics
- Remaining Device Lifetime [see Remaining Device Lifetime (4.2.) on page 99]
- Remaining Sensor Lifetime [see Remaining Sensor Lifetime (4.3.) on page 102]
- Service Schedule [see Service Schedule (4.4.) on page 105]
- Calibration Schedule [see Calibration Schedule (4.5.) on page 108]
- Electronic Temperature
- Wear (see Wear on page 56)
- Communication
- Security
- Device Diagnostics
- AMS Menu Structure
- Functions in AMS Device Manager
- Parameter Reference
- 1. Quick Start
- 2. Setup
- 3. Diagnostics
- 4. Service
- 5. Communication
- 6. Security
- 7. Language
- Appendix A: Alphabetical Parameter List
- Appendix B: Troubleshooting
- Appendix C: Maintenance
- Appendix D: Technical Reference
- Principles of Operation
- Echo Processing
- Analog Output
- Maximum Process Temperature Chart
- Process Pressure/Temperature derating curves
- Loop power
- Appendix E: Application Examples
- Appendix F: HART Communications
- Appendix G: ATEX Certificates
- Appendix H: Firmware Revision History
- Glossary
- Index
- LCD menu structure
7ML19985JE03 SITRANS LR250 (HART) – INSTRUCTION MANUAL Page 83
mmmmm
Parameters
2.5. Fail-safe
2.5.1. Material Level
Defines the mA output to use when the Fail-safe Timer expires.
2.5.2. Timer
Sets the time to elapse since the last valid reading, before the Fail-safe Level is
reported.
2.5.3. Level
Allows the user to define the mA value to be reported when the Fail-safe timer
expires.
Note: Default settings in the parameter tables are indicated with an asterisk (*)
unless explicitly stated.
Note: The default setting depends whether your device is a standard or
NAMUR NE 43-compliant device.
STANDARD DEVICE
Options
HI 20.5 mA (max. mA Limit)
LO 3.8 mA (min. mA Limit)
*HOLDLast valid reading (default 22.6 mA)
VALUE User-selected value [defined in Level (2.5.3.)]
NAMUR NE 43-COMPLIANT DEVICE
Options
HI 20.5 mA (max. mA Limit)
LO 3.8 mA (min. mA Limit)
HOLD Last valid reading
* VALUE
User-selected value [defined in Level (2.5.3.): default
3.58 mA]
Note: When a Loss of Echo occurs Material Level (2.5.1.) determines the
material level to be reported when the Fail-safe timer expires. See
Loss of
Echo (LOE)
on page 134 for more detail.
Values
Range: 0.00 to 7200 seconds
Default: 100 s
Notes:
• The default setting depends whether your device is a standard or NAMUR
NE 43-compliant device.
• Material Level (2.5.1.) must be set to VALUE to enable the Level value to be
reported.
Device Type
STANDARD
NAMUR NE43-
COMPLIANT
Values
Range 3.56 mA to 22.6 mA
Default 22.60 mA 3.58 mA