User's Manual
Table Of Contents
- Table of Contents
- SITRANS LR250 Overview
- Specifications
- Installation
- Wiring
- Operating via the handheld programmer
- Operating via SIMATIC PDM
- Functions in SIMATIC PDM
- Quick Start Wizard via SIMATIC PDM
- Changing parameter settings using SIMATIC PDM
- Parameters accessed via pull-down menus
- Operating via AMS Device Manager
- Functions in AMS Device Manager
- Features of AMS Device Manager
- Device Description (DD)
- Configuring a new device
- Startup
- Pull-down menu access
- Device configuration
- Quick Start Wizard via AMS Device Manager
- Maintenance and Diagnostics
- Remaining Device Lifetime [see Remaining Device Lifetime (4.2.) on page 99]
- Remaining Sensor Lifetime [see Remaining Sensor Lifetime (4.3.) on page 102]
- Service Schedule [see Service Schedule (4.4.) on page 105]
- Calibration Schedule [see Calibration Schedule (4.5.) on page 108]
- Electronic Temperature
- Wear (see Wear on page 56)
- Communication
- Security
- Device Diagnostics
- AMS Menu Structure
- Functions in AMS Device Manager
- Parameter Reference
- 1. Quick Start
- 2. Setup
- 3. Diagnostics
- 4. Service
- 5. Communication
- 6. Security
- 7. Language
- Appendix A: Alphabetical Parameter List
- Appendix B: Troubleshooting
- Appendix C: Maintenance
- Appendix D: Technical Reference
- Principles of Operation
- Echo Processing
- Analog Output
- Maximum Process Temperature Chart
- Process Pressure/Temperature derating curves
- Loop power
- Appendix E: Application Examples
- Appendix F: HART Communications
- Appendix G: ATEX Certificates
- Appendix H: Firmware Revision History
- Glossary
- Index
- LCD menu structure
Page 146 SITRANS LR250 (HART) – INSTRUCTION MANUAL 7ML19985JE03
mmmmm
F: HART Communications
Appendix F: HART Communications
Highway Addressable Remote Transducer, HART, is an industrial protocol that is
superimposed on the 4-20 mA signal. It is an open standard, and full details about HART
can be obtained from the HART Communication Foundation at www.hartcomm.org
SITRANS LR250 can be configured over the HART network using either the HART
Communicator 375 by Fisher-Rosemount, or a software package. The recommended
software package is the SIMATIC Process Device Manager (PDM) by Siemens.
SIMATIC PDM
This software package is designed to permit easy configuration, monitoring, and
troubleshooting of HART devices. The HART EDD for SITRANS LR250 was written with
SIMATIC PDM in mind and has been extensively tested with this software.
For more information, see
Operating via SIMATIC PDM
on page 40.
HART Electronic Device Description (EDD)
In order to configure a HART device, the configuration software requires the HART
Electronic Device Description for the instrument in question.
You can download the HART EDD for SITRANS LR250 from the product page of our
website. Go to: www.siemens.com/LR250
and click on Downloads.
Older versions of the library will have to be updated in order to use all the features of
SITRANS LR250.