Page 124 SITRANS LR250 (HART) – INSTRUCTION MANUAL 7ML19985JE03
mmmmm
B: Troubleshooting
Reading response slow
Fill Rate (2.4.2.) setting incor-
rect
increase measurement response if possi-
ble
Reads correctly but occa-
sionally reads high when
vessel is not full
detecting close range
echo
build up near top of
vessel or nozzle
nozzle problem
clean the antenna
•use Auto False Echo Suppression (2.8.7.1.)
and Auto False Echo Suppression Range
(2.8.7.2.)
Level reading lower than
actual material level
material is within Near
Range zone
multiple echoes
processed
decrease Near Range (2.8.1.) (minimum
value depends on antenna type)
raise SITRANS LR250
ensure Algorithm (2.8.4.1.) is set to F (First
echo)
vessel near empty and
low dK material
ensure Material (2.2.3.) selection is LIQ-
UID LOW DK
•set Position Detect (2.8.4.2.) to Hybrid
•set CLEF Range (2.8.4.4.) to 0.5 m
Operation Troubleshooting (cont’d)
Symptom Cause Action