User's Manual

Table Of Contents
Technical data
11.3 Interface
SITRANS LR250 (HART)
Operating Instructions, 01/2014, A5E32220602-AB
183
11.3
Interface
Analog output
Signal range
4 to 20 mA (± 0.02 mA accuracy) upper limit 20 to 23 mA adjustable
Fail signal
3.6 mA to 23 mA [For more details, see Fail-safe Mode] (Page 227)
Communication:
HART
1)
Load
230 to 600 Ω, 230 to 500 Ω when connecting a coupling module
Max. line length
multi-wire: ≤ 1500 m (4921 ft)
Protocol
HART, Version 5.1
Configuration
Remote
Siemens SIMATIC PDM or AMS Device Manager (PC)
Local
Siemens infrared handheld programmer, or HART handheld communicator
Display (local)
2)
graphic LCD, with bar graph representing level
1)
See A.6.3 for details on version exclusions
2)
Display quality will be degraded in temperatures below 25 °C (13 °F) and above +65 °C (+149 °F).
Curve 2 (Flameproof, Increased Safety, Explosion-proof) (Page 238)