User's Manual
Table Of Contents
- 8 Parameter reference
- 9 Service and maintenance
- 10 Diagnosing and troubleshooting
- 11 Technical data
- 12 Dimension drawings
- 12.1 Threaded horn antenna
- 12.2 Threaded horn antenna with extension
- 12.3 Flanged horn antenna
- 12.4 Flanged horn antenna with extension
- 12.5 Flanged encapsulated antenna (2"/DN50/50A sizes only)
- 12.6 Flanged encapsulated antenna (3"/DN80/80A sizes and larger)
- 12.7 Threaded PVDF antenna
- 12.8 Threaded connection markings
- 12.9 Raised-Face flange per EN 1092-1 for flanged horn antenna
- 12.10 Raised-Face flange per EN 1092-1 for flanged encapsulated antenna
- 12.11 Flat-Face flange
- 12.12 Process connection tag (pressure rated versions)
- A Appendix A: Technical reference
- B Appendix B: HART communications
- C Appendix C: Certificates and support
- 13 List of abbreviations
- 14 LCD menu structure
- Glossary
- Index
Parameter reference
SITRANS LR250 (HART)
Operating Instructions, 01/2014, A5E32220602-AB
119
Rate (2.4.)
Response Rate (2.4.1.)
Note
Changing Response Rate resets
Fill Rate per Minute (2.4.2.)
,
Empty Rate per Minute
(2.4.3.)
, and
Damping Filter (2.2.4.)
.
Sets the reaction speed of the device to measurement changes.
Response Rate (2.4.1.)
Fill Rate per Minute
(2.4.2.)
Empty Rate per
Minute (2.4.3.)
Damping Filter (2.2.4.)
*
Slow
0.1 m/min (0.32 ft/min)
10 s
Medium
1.0 m/min (3.28 ft/min)
10 s
Fast
10.0 m/min (32.8 ft/min)
0 s
Use a setting just faster than the maximum filling or emptying rate (whichever is faster).
Fill Rate per Minute (2.4.2.)
Defines the maximum rate at which the reported sensor value is allowed to decrease. Allows you
to adjust the SITRANS LR250 response to decreases in the actual material level. Fill Rate is
automatically updated whenever Response Rate is altered.
Options
Range: 0 to 99999 m / min.
Response Rate (2.4.1.)
Fill Rate per Minute (2.4.2.)
*
Slow
0.1 m/min (0.32 ft/min)
Medium 1.0 m/min (3.28 ft/min)
Fast
10.0 m/min (32.8 ft/min)
Altered by:
Response Rate (2.4.1.)
Related parameters
Units (2.2.1.)
Enter a value slightly greater than the maximum vessel-filling rate, in units per minute.
Sensor value is the value produced by the echo processing which represents the distance from
sensor reference point to the target. See
Sensor Mode (2.2.2.)
for an illustration.