Diagnosing and troubleshooting
10.4 Operation troubleshooting
SITRANS LR250 (HART)
Operating Instructions, 01/2014, A5E32220602-AB
179
Symptom
Cause
Action
Reading erratic echo confidence weak
refer to
Confidence (2.8.6.1.)
use
Auto False Echo Suppression (2.8.7.1.)
and
Auto
False Echo Suppression Range (2.8.7.2.)
use foam deflector or stillpipe
liquid surface vortexed
decrease
Fill Rate per Minute (2.4.2.)
relocate device to side pipe
increase confidence threshold in
Echo Threshold (2.8.4.3.)
material filling
Re-locate SITRANS LR250
Reading response
slow
Fill Rate per Minute (2.4.2.)
setting incorrect
increase measurement response if possible
Reads correctly but
occasionally reads
high when vessel is
not full
detecting close range echo
build up near top of vessel or
nozzle
nozzle problem
clean the antenna
use
Auto False Echo Suppression (2.8.7.1.)
and
Auto
False Echo Suppression Range (2.8.7.2.)
Level reading lower
than actual material
level
material is within Near Range
zone
multiple echoes processed
decrease
Near Range (2.8.1.)
(minimum value depends
on antenna type)
raise SITRANS LR250
ensure
Algorithm (2.8.4.1.)
is set to F (First echo)
vessel near empty and low
dK material
ensure
Material (2.2.3.)
selection is LIQUID LOW DK
set
Position Detect (2.8.4.2.)
to Hybrid
set
CLEF Range (2.8.4.4.)
to 0.5 m