Parameter reference
SITRANS LR250 (HART)
144 Operating Instructions, 01/2014, A5E32220602-AB
Service (4.)
Note
Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly
stated.
Master Reset (4.1.)
Note
Following a reset to Factory Defaults
, complete reprogramming is required.
Resets all parameter to factory defaults, with the following exceptions:
Device Address (5.1.)
remains unchanged if the reset command is sent remotely (via AMS,
PDM, DTM, FC375) but is reset to 0 if the reset command is sent via LUI.
Write Protect (6.2.1.)
and
PIN to Unlock (6.2.2.)
values are not reset.
Auto False Echo Suppression (2.8.7.1.)
learned TVT and
Auto False Echo Suppression
Range (2.8.7.2.)
are not lost.
Options
*
Idle or Done (Return to previous menu)
Factory Defaults
To perform a reset to factory defaults via SIMATIC PDM, open the menu
Device Master Reset
and click on
Factory Defaults.