User's Manual
Table Of Contents
- 8 Parameter reference
- 9 Service and maintenance
- 10 Diagnosing and troubleshooting
- 11 Technical data
- 12 Dimension drawings
- 12.1 Threaded horn antenna
- 12.2 Threaded horn antenna with extension
- 12.3 Flanged horn antenna
- 12.4 Flanged horn antenna with extension
- 12.5 Flanged encapsulated antenna (2"/DN50/50A sizes only)
- 12.6 Flanged encapsulated antenna (3"/DN80/80A sizes and larger)
- 12.7 Threaded PVDF antenna
- 12.8 Threaded connection markings
- 12.9 Raised-Face flange per EN 1092-1 for flanged horn antenna
- 12.10 Raised-Face flange per EN 1092-1 for flanged encapsulated antenna
- 12.11 Flat-Face flange
- 12.12 Process connection tag (pressure rated versions)
- A Appendix A: Technical reference
- B Appendix B: HART communications
- C Appendix C: Certificates and support
- 13 List of abbreviations
- 14 LCD menu structure
- Glossary
- Index
Parameter reference
SITRANS LR250 (HART)
Operating Instructions, 01/2014, A5E32220602-AB
139
To set Auto False Echo Suppression via the handheld programmer:
Options
OFF
Default TVT will be used.
*
ON
’Learned’ TVT will be used.
LEARN
’Learn’ the TVT
a)
.
a)
The learned TVT takes effect only at the next measurement.
Auto False Echo Suppression Range (2.8.7.2.)
Note
Changes take effect only at the next measurement. "Master reset" does no
t clear the
learned/stored TVT, select "Off" to turn it off or "learn" for a new TVT.
See
Master Reset
(4.1.)
Specifies the range within which Learned TVT is used [see
Auto False Echo Suppression
(2.8.7.1.)
for more detail].
Values
Range: 0.00 to 20.00 m
Default: 1.00 m
Related parameters
Units (2.2.1.)
1. Calculate range according to
Auto False Echo Suppression (2.8.7.1.)
steps 1 and 2.
2. Press
RIGHT arrow
to open Edit mode.
3. Enter the new value and press
RIGHT arrow
to accept it.
4. Set
Auto False Echo Suppression (2.8.7.1.)
.