Parameter reference
SITRANS LR250 (PROFIBUS PA)
Operating Instructions, 01/2014, A5E32221386-AB
121
Input Scaling (2.6.5.)
Upper Value (2.6.5.1.)
Defines the operational upper range value of the input value (Process Value Scale) in PV
(volume/level) Units. Process Value Scale normalizes the input value to a customer-defined
range.
Values
Range: -999999 to 999999
Default: 100%
Provides Output values
(Out) to AIFB1
or AIFB2
Lower Value (2.6.5.2.)
Defines the operational lower range value of the input value (Process Value Scale) in PV
(volume/level) Units. Process Value Scale normalizes the input value to a customer-defined
range.
Values
Range: -999999 to 999999
Default: 0%
Output Scaling (2.6.6.)
Scales the Process Variable. The function block parameter OUT SCALE contains the values of
the lower limit and upper limit effective range in AIFB1 units.