Parameter reference
SITRANS LR250 (PROFIBUS PA)
118 Operating Instructions, 01/2014, A5E32221386-AB
Shaper Mode (2.5.10.4.)
Enables/disables
TVT shaper
(2.5.11.)
Options
ON
*
OFF
TVT shaper (2.5.11.)
Note
The range is 50 to 50 dB.
Shaper Mode (2.5.10.4.)
must be turned
ON
in order for TVT shaper points to be
transferred.
Adjusts the TVT (Time Varying Threshold) at a specified range (breakpoint on the TVT). This
allows you to reshape the TVT to avoid unwanted echoes. There are 40 breakpoints arranged in
5 groups. (We recommend using SIMATIC PDM to access this feature.)
To use TVT shaper via SIMATIC PDM:
1. Go to
Level Meter > Setup > Signal Processing > TVT setup > Shaper Mode
and select
On
.
2. Open the menu
Device Echo Profile Utilities
and click on TVT Shaper. For more detail see
TVT Shaper via SIMATIC PDM (Page 72).
To use TVT shaper via LUI (local user interface):
1. Go to
Shaper Mode (2.5.10.4.)
and select
ON
.
2. In TVT shaper, go to
Breakpoints
1-9 (2.5.11.1.)
.
3. Open Breakpoint 1 and enter the TVT Offset value (between 50 and 50 dB).
4. Go to the next Breakpoint and repeat step 3 until all desired breakpoint values have been
entered.
Breakpoint 1-9 (2.5.11.1.)
Values
Range: 50 to 50 dB
Default: 0 dB