Condensed status
These codes are available when Condensed Status is enabled. See
Condensed Status (3.4.)
for
more details.
Condensed Status (GOOD)
Hex value
Status - GOOD
Description
0x80
GOOD ok
No error or special condition is associated with this value.
0x84 GOOD update event Set if the value is good and the block has an active Update
event. (This status remains active for 20 seconds.)
0x86 GOOD active
advisory alarm
Set if the value is good and the block has an active Alarm.
0x80
...0x8E
GOOD limit check/
update event
See Status Codes for Good Quality (Page 234).
0xA0
...0xA3
GOOD initiate fail
safe
This fault is not generated by the product, but can be
simulated.
0xA4
...0xA7
GOOD maintenance
required
Value is valid. Maintenance is recommended within a
medium-term period.
0xA8
...0xAB
GOOD maintenance
demanded
Value is valid. Maintenance is demanded within a short- term
period.
0xBC
...0xBF
GOOD function
check
Device performs internal function check without influencing
the process. Value is valid.
Condensed Status (UNCERTAIN)
Hex value
Status - UNCERTAIN
Description
0x45 UNCERTAIN
substitute set
Output of Failsafe logic only.
0x4F UNCERTAIN initial
value
Default value as long as no measured value is available or
until a diagnosis is made that a
ffects the value and the status
accorded to it.
0x68
...0x6B
UNCERTAIN
maintenance
demanded
Usability of the process value depends on the application.
Value is potentially invalid. Cause can be determined by
reading the extended diagnostics
a)
. Maintenance is
demanded within a short-term period.