User's Manual

Table Of Contents
Parameter reference
SITRANS LR250 (PROFIBUS PA)
106 Operating Instructions, 01/2014, A5E32221386-AB
XY index (2.4.1.5.)
Level/Volume breakpoints allow you to define a complex vessel shape as a series of segments.
A value is assigned to each level breakpoint and a corresponding value is assigned to each
volume breakpoint.
Volume values are defined in volume units and can be percent or volumetric; level values are
defined in level units, and can be percent or linear. See
Level Unit (2.3.2.)
and
PV Units
(volume/level) (2.3.3.)
.
Level values
Range: -999999.00 to 999999.00 (m, cm, mm, ft, in, %)
Default: 0.0
Volume values
Range: -999999.00 to 999999.00 (% or volumetric units)
Default: 0.0
Enter up to 32 level breakpoints, where the corresponding volume is known. The values
corresponding to 100% and 0% levels must be entered. The breakpoints can be ordered from
top to bottom, or the reverse.
Example (values are for example purposes only)
Breakpoint Number
Level value (m)
Volume value (l)
1
0
0
2
5
500
3
9
3000
4
19.5
8000