User's Manual
Table Of Contents
- 8 Parameter reference
- 9 Service and maintenance
- 10 Diagnosing and troubleshooting
- 11 Technical data
- 12 Dimension drawings
- 12.1 Threaded horn antenna
- 12.2 Threaded horn antenna with extension
- 12.3 Flanged horn antenna
- 12.4 Flanged horn antenna with extension
- 12.5 Flanged encapsulated antenna (2"/DN50/50A sizes only)
- 12.6 Flanged encapsulated antenna (3"/DN80/80A sizes and larger)
- 12.7 Threaded PVDF antenna
- 12.8 Threaded connection markings
- 12.9 Raised-Face flange per EN 1092-1 for flanged horn antenna
- 12.10 Raised-Face flange per EN 1092-1 for flanged encapsulated antenna
- 12.11 Flat-Face flange
- 12.12 Process connection tag (pressure rated versions)
- A Appendix A: Technical reference
- B Appendix B: PROFIBUS PA profile structure
- C Appendix C: Communications via PROFIBUS
- D Appendix D: Certificates and Support
- 13 List of abbreviations
- 14 LCD menu structure
- Glossary
- Index
Parameter reference
SITRANS LR250 (PROFIBUS PA)
Operating Instructions, 01/2014, A5E32221386-AB
105
Maximum Volume (2.4.1.2.)
The maximum volume of the vessel. Units are defined in
PV Units (volume/ level) (2.3.3.)
. Enter
the vessel volume corresponding to High Calibration Point. The volume calculation is based on
the maximum volume and scaled according to the vessel shape selected. If no vessel shape is
entered, the default is 100, and the reading will be a percentage value.
Values
Range: 0.0000 to 999999
Default: 100.0
Related Parameters
Low Calibration Pt. (2.3.7.1.)
High Calibration Pt. (2.3.7.2.)
Vessel Shape (2.4.1.1.)
For readings in volumetric units instead of percentage values:
1. Select a volumetric unit from
PV Units (volume/level) (2.3.3.)
.
2. Enter the vessel volume corresponding to High Calibration Point.
Dimension A (2.4.1.3.)
The height of the vessel bottom in Level Units when the bottom is conical, pyramidal, parabolic,
spherical, or flat -sloped. If the vessel is horizontal
with parabolic ends, the depth of the end. See
Vessel Shape (2.4.1.1.)
for an illustration.
Values
Range: 0.0000 to 999999 in Level Units
Default: 0.0
Related Parameters
Vessel Shape (2.4.1.1.)
Dimension L (2.4.1.4.)
Length of the cylindrical section of a horizontal parabolic end vessel, in Level Units. See
Vessel
Shape (2.4.1.1.)
for an illustration.
Values
Range: 0.0000 to 999999 in Level Units
Default: 0.0
Related Parameters
Vessel Shape (2.4.1.1.)