User's Manual
Table Of Contents
- 8 Parameter reference
- 9 Service and maintenance
- 10 Diagnosing and troubleshooting
- 11 Technical data
- 12 Dimension drawings
- 12.1 Threaded horn antenna
- 12.2 Threaded horn antenna with extension
- 12.3 Flanged horn antenna
- 12.4 Flanged horn antenna with extension
- 12.5 Flanged encapsulated antenna (2"/DN50/50A sizes only)
- 12.6 Flanged encapsulated antenna (3"/DN80/80A sizes and larger)
- 12.7 Threaded PVDF antenna
- 12.8 Threaded connection markings
- 12.9 Raised-Face flange per EN 1092-1 for flanged horn antenna
- 12.10 Raised-Face flange per EN 1092-1 for flanged encapsulated antenna
- 12.11 Flat-Face flange
- 12.12 Process connection tag (pressure rated versions)
- A Appendix A: Technical reference
- B Appendix B: Communications via Foundation Fieldbus
- C Appendix C: Certificates and support
- 13 List of abbreviations
- 14 LCD menu structure
- Glossary
- Index
Diagnosing and troubleshooting
10.2 General fault codes
SITRANS LR250 (FOUNDATION FIELDBUS)
Operating Instructions, 01/2014, A5E32221411-AB
191
Code/
Icon
Meaning
Corrective Action
S: 10
Input parameters
Low Calibration Point (2.3.7.1.)
and
High Calibration Point (2.3.7.2.)
are the
same.
• Check calibration settings of device.
• Ensure settings for High Calibration Point and Low
Calibration Point are different.
S: 11
Internal temperature sensor failure. Repair required: contact your local Siemens representative.
S: 12
Internal temperature of device has exceeded
specifications: it is operating outside its
temperature range.
• Relocate device and/or lower process temperature
enough to cool device.
• Inspect for heat-related damage and contact your local
Siemens representative if repair is required.
• Fault code will persist until a manual reset is performed
using AMS or the LCD interface.
S: 17
Calibration interval (4.5.1.)
has
expired and has triggered a
Maintenance
Required reminder (4.5.5.)
.
Perform calibration.
S: 18
Calibration interval (4.5.1.)
has
expired and has triggered a
Maintenance
Demanded reminder (4.5.6.)
.
Perform calibration.
S: 22
Time Base Fault Hardware problem: contact your local Siemens
representative.
S: 28
Internal device failure caused by a RAM memory
error.
Repair required: contact your local Siemens representative.
S: 29
EEPROM damaged. Repair required: contact your local Siemens representative
S: 31
Flash error. Repair required: contact your local Siemens representative
S: 33
Factory calibration for the internal temperature
sensor has been lost.
Repair required: contact your local Siemens representative
S: 34
Factory calibration for the device has been lost. Repair required: contact your local Siemens representative