Diagnosing and troubleshooting
10.2 General fault codes
SITRANS LR250 (FOUNDATION FIELDBUS)
190 Operating Instructions, 01/2014, A5E32221411-AB
10.2
General fault codes
Note
If more than one fault is present, the device status indicator and text for each fault
alternate at 2 second intervals.
Code/
Icon
Meaning
Corrective Action
S: 0
The device was unable to get a measurement
within the Fail-safe LOE Timer period. Possible
causes: faulty installation, antenna material
buildup, foaming/other adverse process
conditions, invalid configuration range.
Ensure installation details are correct.
Ensure no antenna material buildup. Clean if necessary.
Adjust process conditions to minimize foam or other
adverse conditions.
Correct configuration range.
If fault persists, contact your local Siemens
representative.
S: 2
Unable to collect profile because of a power
condition that is outside the operating range of
the device.
Repair required: contact your local Siemens representative.
S: 3
Device is nearing its lifetime limit as defined in
Remaining Lifetime (4.2.3.)
and has triggered a
Maintenance Required reminder (4.2.5.)
.
Replacement is recommended
S: 4
Device is nearing its lifetime limit as defined in
Remaining Lifetime (4.2.3.)
and has triggered a
Maintenance Demanded reminder (4.2.6.)
.
Replacement is recommended.
S: 6
Sensor is nearing its lifetime limit as defined in
Remaining Lifetime (4.3.3.)
and has triggered a
Maintenance Required reminder (4.3.5.)
.
Replacement is recommended.
S: 7
Sensor is nearing its lifetime limit as defined in
Remaining Lifetime (4.3.3.)
and has triggered a
Maintenance Demanded reminder (4.3.6.)
.
Replacement is recommended.
S: 8
Service interval (4.4.1.)
has expired and has
triggered a
Maintenance Required reminder
(4.4.5.)
.
Perform service.
S: 9
Service interval (4.4.1.)
has expired and has
triggered a
Maintenance Demanded reminder
(4.4.6.)
.
Perform service.