Parameter reference
SITRANS LR250 (FOUNDATION FIELDBUS)
134 Operating Instructions, 01/2014, A5E32221411-AB
Calibration (2.3.7)
Low Calibration Pt. (2.3.7.1.)
Distance from sensor reference point to Low Calibration Point (corresponding to Low Level
Point). Units are defined in
Unit (2.3.1.).
High level point (default 100%)
Level offset (if used)
Low level point (0%)
Low calibration point
Sensor value
Sensor reference point
a)
High calibration point
Far range
Level
a)
The point from which level measurement is referenced [see Flat Faced Flange (Page 225) and
Threaded Horn Antenna with extension (Page 205) and Flanged encapsulated antenna
(3"/DN80/80A sizes and larger). (Page 216) ].
Values
Range: 0.00 to 20.00 m. Default 20.00 m
Related parameters
Unit (2.3.1.)
Far Range (2.5.2.)