User's Manual

Table Of Contents
Parameter reference
SITRANS LR250 (FOUNDATION FIELDBUS)
150 Operating Instructions, 01/2014, A5E32221411-AB
Auto False Echo Suppression (2.5.10.1.)
Used together with
Auto False Echo Suppression Range (2.5.10.2.)
to screen out false echoes
in a vessel with known obstructions. A ’learned TVT’ (time varying threshold) replaces the
default TVT over a specified range. See
Auto False Echo Suppression (Page 236) for a more
detailed explanation.
Before Auto False Echo Suppression
TVT Hover Level
echo marker
default TVT
material level
false echo
1. Determine Auto False Echo Suppression Range. Measure the actual distance from the
sensor reference point to the material surface using a rope or tape measure.
2. Subtract 0.5 m (20") from this distance, and use the resulting value.