User's Manual

Table Of Contents
Parameter reference
SITRANS LR250 (FOUNDATION FIELDBUS)
Operating Instructions, 01/2014, A5E32221411-AB
149
Echo Quality (2.5.9.)
Confidence (2.5.9.1.)
Indicates echo reliability: higher values represent better echo quality. The display shows the
echo confidence of the last measurement.
Echo Threshold (2.5.7.3.)
defines the minimum
criterion for echo confidence.
Values
(view only)
0
to
99
Echo Threshold (2.5.7.3.)
Related Parameters
Open the menu
Device Echo Profile Utilities
and click on the tab
Echo Profile
.
Echo Strength (2.5.9.2.)
Displays the absolute strength (in dB above 1 μV rms) of the echo selected as the measurement
echo.
Values
(view only)
Range:
20
to
99
TVT (Auto False Echo Suppression) Setup (2.5.10.)
Note
Make sure material level is below all known obstructions when Auto False Echo
Suppression is used to learn the echo profile. (An empty
or almost empty vessel is recommended.)
Note the distance to material level when Auto False Echo learns the environment. Set
Auto False Echo Suppression Range to a shorter
distance to avoid the material echo being screened out.
Set Auto False Echo Suppression and Auto False Echo Suppression Range during
startup, if possible.
If the vessel contains an agitator it should be running.
Before adjusting these parameters, rotate the instrument for best signal (lower false-
echo
amplitude).