Parameter reference
SITRANS LR250 (FOUNDATION FIELDBUS)
Operating Instructions, 01/2014, A5E32221411-AB
143
Far Range (2.5.2.)
Note
Far Range can extend beyond the bottom of the vessel.
Allows the material level to drop below Low Calibration Point without generating a Loss of Echo
(LOE) state. See
Low Calibration Pt. (2.3.7.1.)
for an illustration.
Values
Range: Min. =
Low Calibration Pt.
Max. =
33
m (108.27 ft)
Default: Value for Low Calibration Pt. + 1 m (3.28 ft)
Related parameters
Unit (2.3.1.)
CLEF (Constrained Leading Edge Fit) Range (2.5.7.4.)
a)
a)
The value set for Far Range becomes the CLEF Range maximum. If the value for Far Range is
changed after a CLEF Range value is entered, CLEF Range is reset to its default (0.00 m).
Use this feature if the measured surface can drop below the Low calibration point in normal
operation.